Veritas NetBackup™ 5240 Appliance Hardware Installation Guide
- Hardware overview
- Preinstallation requirements
- Customer-provided environment and supplies
- Storage shelf shipping container contents
- Appliance shipping container contents
- Enabling SAS tape-out functionality
- Determining rack locations
- Best practices for rack installation
- Heat dissipation
- Verifying SAS-3 cable length
- Prerequisites for IPMI configuration on a 52xx and 5330
- Installation procedures
- Installing the storage shelf rack rails
- Installing the storage shelf into a rack
- Installing the appliance rack rails
- Installing the appliance into a rack
- Attaching the storage shelf bezel
- Understanding appliance and storage shelf connections
- Connecting an appliance to one storage shelf
- Connecting an appliance to more than one storage shelf
- Connecting the network cables
- Connecting the power cords
- Turning on the hardware and verifying operation
- Configuring the IPMI port from the NetBackup Appliance Shell Menu
- Accessing and using the Veritas Remote Management interface
- Appendix A. Adding one or more storage shelves to an operating appliance that does not have any storage shelves
- Overview
- Preparing the appliance
- Removing the appliance cover
- Installing the Expansion Storage Kit components
- Reinstalling the appliance into the rack
- Storage shelf rack requirements
- Determining rack locations
- Installing the storage shelf rails
- Installing the storage shelf or shelves into a rack
- Understanding appliance and storage shelf connections
- Connecting one storage shelf to an appliance
- Connecting two storage shelves to an appliance
- Connecting three storage shelves to an appliance
- Connecting four storage shelves to an appliance
- Connecting the network cables
- Connecting the power cords
- Turning on the hardware and verifying operation
- Appendix B. Adding storage shelves to an operating appliance that has at least one storage shelf attached
- Appendix C. Adding the disk space of additional storage shelves
- Index
Heat dissipation
Air flows from the front of each unit and exits from the rear of each unit. You can install the optional bezel without disruption to the airflow.
For best ventilation, the rack cabinet should:
Be at least 100 cm (4 feet) from walls.
Be at least 100 cm (4 feet) from other cabinets on the front and back of the appliance and the storage shelves.
Note:
Data centers with two-foot spaces in the front and in the back of the appliances are acceptable with proper cooling and ventilation.
Veritas provides the following requirements to ensure sufficient cooling.
Veritas requires that you install the system in a National Engineering Manufacturer's Association (NEMA)-certified or equivalent rack.
A minimum of 3 inches (7.6 cm) of space must be between the front of an appliance and the cabinet door or other air block.
A minimum of 6 inches (15.2 cm) of space must be between the rear of an appliance and the cabinet rear or other air block.
A minimum of 1 inch (2.5 cm) of space must be between the front of a storage shelf and the cabinet door or other air block.
A minimum of 2 inches (5.0 cm) of space must be between the rear of a storage shelf and the cabinet rear or other air block.
Refer to the NetBackup 5240 Appliance Product Description Guide for specifications about temperature and cooling.